Generator > PT 300 KVA

« Back to Generators Main Page

SPECS

300 KVA 50 Hz
PT 300  
Engine Model 2306C-E14TAG1 Perkins
Alternator Model 46.2 VL12 LSA
Continuous Power 300 KVA / 240 KW
Standby Power 350 KVA / 280 KW
Prime / Standby bhp 350 / 408
Stroke 4
Nb. Of cylinders 6
Cylinder arrangement Vertical In-Line
Bore x Stroke 137 x 165 mm
Swept Volume 14.6 Ltrs
Combustion System Direct Injection
Aspiration Turbo Air To Air After Cooled
Governor Electronic
Electrical System 24 Volts
Engine Oil Capacity 68 Ltrs
Total Coolant Capacity 47 Ltrs
Fuel Consumption 62.4 Ltrs / hr
Fuel Tank Capacity 270 Ltrs
Alternator Voltage Regualtion ± 1%
Shipping Dimensions Length 330 cm
Width 101 cm
Height 185 cm
Weight 2900 Kg

Rating

The ratings represent the Engine capabilities within - + 5% at NTP conditions equivalent to those specified in ISO3046,BS5514,DIN 6271, and subject to duration under extreme environmental conditions .

Engine

Perkins multi cylinder, 4 stroke, water cooled diesel engine complete with electric starter, starter solenoid relay, battery charge alternator replaceable fuel, oil and air filters, primary water separator, fuel lift pump, sensors connection for low lub oil pressure, high coolant temperature, sump drain tap, loose supplied industrial exh. silencer.

Radiator

Set mounted tropical radiator core design suitable for 50oc max T° air inlet with engine driven cooling fan and fan guard.

Batteries

Heavy duty lead acid batteries complete with battery rack and connecting cables.

Alternator

Leroy Somer, single bearing, brushless, synchronous, self excited, self regulated, screen protected, drip proof enclosure IP21 and IP23 temperature rise class H, and insulation class H. -Line to line voltage wave form distortion is < 3%.

Coupling

Engine and alternator are directly coupled through disc coupling.

Base frame

Set mounted on heavy duty steel base frame with anti-vibration oil proof Rubber mounts between gen-set & base.

Fuel tank

Separate daily fuel tank can be supplied loose as an option complete with filler cap & drain plug and fuel indicator

Control Panel

Set mounted control panel complete with one AC ammeter with selector switch, frequency meter, hour run meter, one AC voltmeter with selector switch, electrical oil pressure gauge, water temperature gauge, battery voltmeter manual key start, automatic shutdown device with indication lamps for LOP/HWT, molded case circuit breaker.

Works-Testing

Each genset is extensively inspected and tested under full load conditions prior to dispatch.

Painted Finish

The diesel engine comes with original black, the alternator with original yellow, the base in black, control panel & circuit breaker enclosure in yellow.

Technical documents

Instruction manuals for the Engine/Alternator as well as use and maintenance of the generating set supplied with each unit.

 

 

Copyright © 2007 Dunia al Iraq. All rights reserved. Powered by SELINCO